1 aizvietošanas variants atrasts

Esošais Sūknis - Cirkulācija

Ražotājs Vecais Wilo
Produkta nosaukums Stratos GIGA 65/1-42/4,5
Artikula Nr. 2117143
Kopējais garums 340 mm
Elektropieslēgums 3x400 V
Caurules pieslēgums DN 65 PN16

Nomaiņas sūknis - High Efficiency Premium Apmaiņats komplekts

Produkta nosaukums Stratos GIGA 65/1-42/4,8
Artikula Nr. 2170127
MEI ≥ 0,7
IE 5
Kopējais garums 340 mm
Elektropieslēgums 3x400 V
Caurules pieslēgums DN 65 PN16
Nominālā strāva 9,1 A
Nominālā jauda P2 4,8 kW
Šķidruma temperatūras diapazons -20 - +140 °C

Komentāri

Saderīgs, neveicot izmaiņas cauruļvadu sistēmā.

Produkta informācija
Stratos GIGA 65/1-42/4,8

Stratos GIGA 65/1-42/4,8
Artikula Nr. : 2170127

Your advantages
  • Innovative high-efficiency pump for maximum overall efficiency levels
  • High-efficiency EC motor with efficiency class IE5 according to IEC 60034-30-2
  • Highest possible operational reliability thanks to standby pump
  • Optional interfaces for connection to building automation using insertable IF modules
Maximum energy efficiency, double safety.

The Wilo-Stratos GIGA is the ideal high-efficiency pump for use in heating, air conditioning and cooling applications in buildings where large volumes of water have to be pumped to great delivery heights. Wilo-Stratos GIGA offers ever greater operational reliability with the standby pump in the twin-head pump version.

Construction
High-efficiency in-line twin-head pump with EC motor and electronic power adjustment in glanded pump construction. Version as single-stage low-pressure centrifugal pump with flange connection and mechanical seal.

Application
The pumping of heating water (in accordance with VDI 2035), cold water and water-glycol mixtures without abrasive substances in heating, cold water and cooling systems.

Equipment/function
Operating modes
  • Δp-c for constant differential pressure
  • Δp-v for variable differential pressure
  • PID-Control
  • Constant speed (n=constant)
Manual operation level
  • Green button and display
Manual functions
  • Differential pressure setpoint setting
  • Setting the speed (manual control mode)
  • Setting the operating mode
  • Setting the pump ON/OFF
  • Configuration of all operating parameters
  • Fault acknowledgement
External control functions
  • "Overriding Off" control input
  • “External pump cycling” control input (only effective in twin-head pump operation)
  • Analogue input 0 – 10 V, 0 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 2 – 10 V, 4 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 0 – 10 V for actual value signal from pressure sensor
  • Analogue input 2 – 10 V, 0 – 20 mA, 4 – 20 mA for actual value signal from pressure sensor
Signal and display functions
  • Collective fault signal SSM
  • Collective run signal SBM
Data exchange
  • Infrared interface for wireless data exchange with IR-Monitor/IR-Stick
  • Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation
Safety functions
  • Full motor protection with integrated trip electronics
  • Access disable
Dual pump management (twin-head pump or 2 x single pumps)
  • Main/standby operation (automatic fault-actuated switchover)
  • Pump cycling main/standby operation after 24 hours
  • Parallel operation
  • Parallel operation (efficiency-optimised peak-load activation and deactivation)
Scope of delivery
  • Pump
  • Installation and operating instructions
  • Technical data 
  • Permitted temperature range of the fluid: -20 °C to +140 °C
  • Mains connection 3~480 V ±10 %, 50/60 Hz, 3~440 V ±10 %, 50/60 Hz, 3~400 V ±10 %, 50/60 Hz, 3~380 V -5 % +10 %, 50/60 Hz
  • Protection class IP55
  • Nominal diameter DN 40 to DN 100
  • Max. operating pressure 16 bar
Materials
  • Pump housing and lantern: EN-GJL-250
  • Impeller: PPS-GF40 or EN-GJL-200 depending on the type
  • Shaft: 1.4122
  • Mechanical seal: AQEGG; other mechanical seals on request
COUNTER FLANGE KIT DN65 PN10
Artikula Nr.: 2105583
Mating flanges:
  • Made of steel.
  • Counter flanges (weld) are delivered complete (in pairs) with bolt, nut and flange gasket.
Flange gasket DN 65 PN6/10
Artikula Nr.: 2151002
Flange gasket DN 65 PN6 / 10, Klingersil:
  • Thickness: 2 mm.
  • Inner diameter: 77 mm.
  • Outer diameter: 115 mm.
IR-MONITOR (D,NL,GB,F)
Artikula Nr.: 2017390
Operating and service unit for wireless remote control and remote diagnosis for all Wilo pumps with infra-red interface.
For all pumps and standard motors for measuring the direction of rotation, rotating field frequency and current operating status.
Direction of rotation checking device also for all conventional pumps with alternating or three-phase motor.
Industrial standard due to its sturdy and robust plastic casing, graphical display with scratch-resistant monitor screen.
 
One-button manual operation level for the Wilo high-efficiency and energy-saving pumps, additional 4 buttons for:
  • IR-Monitor on/off
  • Lighting on/off
  • Information/help
Display/monitor (50 x 50 mm) for displaying:
  • Electrical and hydraulic actual values
  • Power supply and duty point of the pump
  • Statistical values
  • Service information
  • Device settings.
Test functions, such as:
  • Self-test pump
  • Self-test IR-Monitor
  • Battery status check.
IF-Module BACnet
Artikula Nr.: 2097811

Interface modules as retrofittable plug-in modules for extending the communication interfaces of the pump in accordance with various standards and protocol variants according to type key.
IF-Module CAN
Artikula Nr.: 2085044

Interface modules as retrofittable plug-in modules for extending the communication interfaces of the pump in accordance with various standards and protocol variants according to type key.
IF-Module LON
Artikula Nr.: 2022530

Interface modules as retrofittable plug-in modules for extending the communication interfaces of the pump in accordance with various standards and protocol variants according to type key.
IF-Module Modbus
Artikula Nr.: 2097809