1 aizvietošanas variants atrasts

Esošais Sūknis - Cirkulācija

Ražotājs Salmson
Produkta nosaukums DIE 208-19/18,5
Kopējais garums 500 mm
Elektropieslēgums 3x400 V
Caurules pieslēgums DN 80 PN16

Nomaiņas sūknis - High Efficiency Standarta Apmaiņats komplekts

Produkta nosaukums Yonos GIGA2.0-D 80/150-18,5/2
Artikula Nr. 2238064
MEI ≥ 0,4
IE 4
Kopējais garums 440 mm
Elektropieslēgums 3x400 V
Caurules pieslēgums DN 80 PN16
Nominālā strāva 31,2 A
Nominālā jauda P2 18,5 kW
Šķidruma temperatūras diapazons -20 - +140 °C

Nomaiņas papildpiederumi

Starpatloku ieliknis A80-60 Kit DN 80 X 60 mm PN10/16
Artikula Nr. 2085213
Numurs 1

Komentāri

Saderīgs ar nomaiņas piederumiem, neveicot izmaiņas cauruļvadu sistēmā.
If you are pumping chilled water media or special material requirements, please contact Wilo Technical Inside Sales. Replacement pumps designed for glycolin-infused water (max. 50%) have the -S1 extension and a different part number than standard seal pumps. Always consult Wilo when pumping media other than water. 

Produkta informācija
Yonos GIGA2.0-D 80/150-18,5/2

Yonos GIGA2.0-D 80/150-18,5/2
Artikula Nr. : 2238064

Your advantages
  • Energy savings due to integrated electronic power adjustment
  • Simple operation with Green Button Technology and display
  • Various operating modes: main/standby operation and parallel operation
  • Configurable fault response tailored to HVAC applications
  • Integrated full motor protection (PTC thermistor sensor) with trip electronics
Construction
Electronically controlled glanded twin-head pump in in-line design with flange connection and automatic power adjustment.

Application
Pumping of heating water (acc. to VDI 2035), cold water and water/glycol mixtures without abrasive substances in heating, cold water and cooling systems.

Equipment/function
Operating modes:
  • Δp-c for constant differential pressure
  • Δp-v for variable differential pressure
  • PID control
  • Constant speed (n=constant)
Manual operation level
  • Green button and display
Manual functions
  • Differential pressure setpoint setting
  • Setting the speed (manual control mode)
  • Setting the operating mode
  • Setting the pump ON/OFF
  • Configuration of all operating parameters
  • Fault acknowledgement
External control functions
  • "Overriding Off" control input
  • “External pump cycling” control input (effective only in dual pump operation)
  • Analogue input 0 – 10 V, 0 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 2 – 10 V, 4 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 0 – 10 V for actual value signal from pressure sensor
  • Analogue input 2 – 10 V, 0 – 20 mA, 4 – 20 mA for actual value signal from pressure sensor
Signal and display functions
  • Collective fault signal SSM
  • Collective run signal SBM
Data exchange
  • Infrared interface for wireless data exchange with IR-Monitor/IR-Stick
  • Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation
Safety functions
  • Full motor protection with integrated trip electronics
  • Access disable
Dual pump management (twin-head pump or 2 x single pumps)
  • Main/standby operation (automatic fault-actuated switchover)
  • Pump cycling main/standby operation after 24 hours
  • Parallel operation
  • Parallel operation (efficiency-optimised peak-load activation and deactivation)
Scope of delivery
  • Pump
  • Installation and operating instructions
Technical data
  • Permissible temperature range of -20 °C to +140 °C
  • Mains connection
  • 3~440 V ±10 %, 50/60 Hz
  • 3~400 V ±10 %, 50/60 Hz
  • 3~380 V -5 % +10 %, 50/60 Hz
  • Protection class IP 55
  • Nominal diameter DN 40 to DN 200
  • Max. operating pressure 16 bar up to +120 °C, 13 bar up to +140 °C
Materials
  • Pump housing and lantern: EN-GJL-250
  • Impeller:
  • Standard version: EN-GJL-200
  • Special version: Bronze CuSn 10
  • Shaft: 1.4122
  • Mechanical seal: AQEGG; other mechanical seals on request
Description/construction
Single-stage, low-pressure twin-head pump in in-line design with: 
  • Switchover valve
  • Mechanical seal
  • Flange connection
  • Lantern
  • Coupling
  • Drive with integrated electronic speed control
Flange gasket DN 80 PN6/10
Artikula Nr.: 2175880
Flange gasket DN 80 PN6 / 10, Klingersil:
  • Thickness: 2 mm.
  • Inner diameter: 90 mm.
  • Outer diameter: 132 mm.